Spring-return control valve (fail-safe)
RVf
Control valve for steam, water, air and other media, with linear flow. A spring in the motor actuator closes or opens the valve on loss of supply voltage.
- Fail-safe: the spring closes or opens the valve when de-energised
- Medium temperature 2 to 220 °C
- Three-position control or 0/4–20 mA, 0/2–10 V
- Closing force 1 kN or 2 kN
- Power supply 100–240 V AC, 24 V AC or 24 V DC, 5 W
- Two-way or three-way version
Description
RVf is a control valve for steam, water, air and other media, with linear flow. The motor actuator contains a spring that closes or opens the valve on power failure, e.g. shuts off the steam supply.
The actuator is controlled in three-position mode or continuously by a 0/4–20 mA or 0/2–10 V signal. The position transmitter provides a 0/4–20 mA or 0/2–10 V signal. Valve stroke is limited by electronic monitoring of the motor current.
Closing force is 1 kN or 2 kN, stroke 10 or 40 mm, and speed 0.25 to 1.40 mm/s. Ambient temperature may be −20 to 60 °C.
Options: heater, IP67 protection and two volt-free contacts.
Technical data
| Function | Safety closing on loss of supply voltage. Steam shut-off on loss of voltage. |
|---|---|
| FAIL-SAFE | Safety function on power failure, closes or opens. |
| Supply voltage | 100-240 V AC 24 V AC 24 V DC |
| Power consumption | 5W |
| Closing force | 1kN 2kN |
| Stroke | 10/40 mm |
| Speed | 0.25 mm/s 0.45 mm/s 0.50 mm/s 1.00 mm/s 1.40 mm/s |
| Ambient operating temperature | -20 to 60℃ |
| Temperature of controlled medium | 2 to 220℃ |
| Valve position transmitter | 0/4 - 20 mA 0/2 - 10 V |
| Motor actuator control | Input signal: - three-position - continuous 0/4 - 20 mA 0/2 - 10 V |
| Valve stroke limitation | Electronic monitoring of motor current |
| Valve closing force limitation | Electronic Option |
| Options | Heater IP67 protection 2 volt-free contacts |