Skip to content
Name, type or catalogue number

    Popular searches

    ↑↓ selectEnter open/ search from any page

    • RVf — photo 1 of 2
    • RVf — drawing 2 of 2

    Spring-return control valve (fail-safe)

    RVf

    Control valve for steam, water, air and other media, with linear flow. A spring in the motor actuator closes or opens the valve on loss of supply voltage.

    Price from540,00 €+ VAT

    Catalogue number TYPE
    Send an enquiry for this product
    • Fail-safe: the spring closes or opens the valve when de-energised
    • Medium temperature 2 to 220 °C
    • Three-position control or 0/4–20 mA, 0/2–10 V
    • Closing force 1 kN or 2 kN
    • Power supply 100–240 V AC, 24 V AC or 24 V DC, 5 W
    • Two-way or three-way version

    Description

    RVf is a control valve for steam, water, air and other media, with linear flow. The motor actuator contains a spring that closes or opens the valve on power failure, e.g. shuts off the steam supply.

    The actuator is controlled in three-position mode or continuously by a 0/4–20 mA or 0/2–10 V signal. The position transmitter provides a 0/4–20 mA or 0/2–10 V signal. Valve stroke is limited by electronic monitoring of the motor current.

    Closing force is 1 kN or 2 kN, stroke 10 or 40 mm, and speed 0.25 to 1.40 mm/s. Ambient temperature may be −20 to 60 °C.

    Options: heater, IP67 protection and two volt-free contacts.

    Technical data

    FunctionSafety closing on loss of supply voltage. Steam shut-off on loss of voltage.
    FAIL-SAFESafety function on power failure, closes or opens.
    Supply voltage100-240 V AC
    24 V AC
    24 V DC
    Power consumption5W
    Closing force1kN
    2kN
    Stroke10/40 mm
    Speed0.25 mm/s
    0.45 mm/s
    0.50 mm/s
    1.00 mm/s
    1.40 mm/s
    Ambient operating temperature-20 to 60℃
    Temperature of controlled medium2 to 220℃
    Valve position transmitter0/4 - 20 mA
    0/2 - 10 V
    Motor actuator controlInput signal:
    - three-position
    - continuous 0/4 - 20 mA
    0/2 - 10 V
    Valve stroke limitationElectronic monitoring of motor current
    Valve closing force limitationElectronic
    Option
    OptionsHeater
    IP67 protection
    2 volt-free contacts

    Documentation

    01Brochures and catalogues1

    Help with selection

    Describe your application and we will suggest a version and a catalogue number.

    For an accurate reply, please state in your enquiry:

    1. 01The medium and its temperature
    2. 02Measuring range
    3. 03Output signal or power supply
    4. 04Type of mounting and connection
    Enquiry forRVfCat. no. RVf.
    Send an enquiry

    or contact us directly

    Mon – Fri, 7 am – 3 pm