    Microprocessor process PID controller

    OMEGA-5k

    Process PID controller with two universal inputs and a separate input for the position of the electric actuator. Four relays are freely assigned to control or alarms, and in addition to automatic mode it has a manual mode.

    Price from610,00 €+ VAT

    Catalogue number Housings
    Send an enquiry for this product
    • 2 universal inputs, 1 actuator position input, 4 logic inputs
    • 4 relays 250 V / 5 A, freely assignable
    • Four configurable alarms
    • Control of electric actuators with and without feedback
    • Manual and automatic mode, autotuning
    • Optional 0/4–20 mA or 0/2–10 V output and RS-485 Modbus

    Why OMEGA-5k

    • 01

      Valve control

      A separate input reads the position of the electric actuator via a potentiometer. In manual mode you set the valve position yourself.

    • 02

      Relays of your choice

      For each of the four relays you define whether it is driven by the PID or by one of the four alarms.

    • 03

      Two universal inputs

      Thermocouples to ITS-90, Pt100 and standard current and voltage signals, software-configurable.

    Description

    OMEGA-5k is a process PID controller for monitoring and controlling limit values of physical quantities. It is used in glass, plastics and ceramics processing, in the chemical and food industries, boiler construction, mechanical engineering, heating and cooling technology and air conditioning.

    The controller has two universal analogue inputs, software-configurable, for all thermocouples covered by the ITS-90 standard, standard current and voltage signals and the Pt100 sensor. A separate analogue input reads the current position of the electric actuator via potentiometer feedback.

    At the output there are four relays whose action you define freely, e.g. first alarm, PID or third alarm. The optional continuous output provides a standard current or voltage signal, and the measured value or the manipulated variable can be assigned to it.

    In addition to automatic mode there is a manual mode, in which you set the current action of the output yourself, i.e. the position of the electric motorised valve.

    Two four-digit LED displays show the measured value and the setpoint. The manipulated variable can be displayed for information for a few seconds, after which the display returns to the measured value. Parameters are entered with the keypad on the front panel.

    Technical data

    TypeOMEGA-5K
    Power supply230 Vac, 50 Hz
    Front panelMembrane with keypad
    MountingPanel mounting with cut-out
    Housing96 x 96 x 119 mm
    144 x 72 x 120 mm
    72 x 144 x 120 mm
    Class0.3 + 2 digit
    Display13mm red LED display, 4 digits, for the measured value
    10mm green LED display, 4 digits, for the setpoint
    25mm green LED BARGRAPH display (10 steps)
    Input2x universal - software-configurable
    -Current 0-20 mA/4-20 mA
    -Voltage 0-10 V/2-10 V
    -Thermocouples J, K, L, N, E, S, R, T, B
    -Resistance Pt100, potentiometers
    -Other (PWM signal, frequency) on special request
    1x potentiometer or current 0-20 mA/4-20 mA
    4x logic (galvanically isolated)
    levels: = 0-6 Vdc = 12-24 Vdc
    Output4 relays, 250 VAC / 5 A
    0-4-20 mA continuous output (optional)
    0-2-10 V continuous output (optional)
    ControlPID on-off/three-position, relay contact 5 A, 250 V + 2 alarms
    Continuous 0-4-20 mA 0-2-10 V
    Control functionON/OFF, P, PI, PD, PID, adjustable
    DataData retained in E2 memory
    CommunicationRS-485 ModBUS (optional)

    Dimensions

    The drawings are taken from the technical documentation.

    Application examples

    Help with selection

    Describe your application and we will suggest a version and a catalogue number.

    For an accurate reply, please state in your enquiry:

    1. 01The medium and its temperature
    2. 02Measuring range
    3. 03Output signal or power supply
    4. 04Type of mounting and connection
    Enquiry forOMEGA-5kCat. no. 0460.
    Send an enquiry

    or contact us directly

    Mon – Fri, 7 am – 3 pm