Signal converter with galvanic isolation
UN-PSG
Converter for current and voltage signals with galvanic isolation of input and output, isolation voltage 1500 V. The input is universal, and the device can also power a two-wire transmitter.
- Universal input: 0–20 mA, 4–20 mA, 0–60 mV, voltage signals, thermocouples L, J, K, S, Pt100
- Output 0–1 mA, 0–20 mA, 4–20 mA, 0–1 V or 0–10 V
- Input/output isolation voltage 1500 V
- Linearity ±0.2 %
- Two-wire transmitter supply 24 VDC / 40 mA
- Housing 40 × 90 × 108 mm for 35 mm DIN rail
Why UN-PSG
- 01
Galvanic isolation 1500 V
Input and output are galvanically isolated with an isolation voltage of 1500 V. The output current is limited to less than 27 mA, and the current output loop can be up to 600 Ω.
- 02
Universal input
Standard current and voltage signals, thermocouples L, J, K and S, and Pt100. Thermocouple cold junction compensation and lead resistance compensation are built into the device, so the user does not adjust anything.
- 03
Transmitter power supply
The device provides 24 VDC to power a two-wire transmitter in the field, e.g. a pressure transmitter, with a maximum output current of 40 mA.
Description
The converter with galvanic isolation is used where, in addition to signal conversion, the input and output must be galvanically isolated. The isolation voltage is 1500 V.
The input is universal: it supports standard current and voltage signals as well as signals from thermocouples and Pt100 probes. Thermocouple cold junction compensation and lead resistance compensation are built into the device, so the user does not have to adjust anything.
The device can power a transmitter (e.g. a pressure transmitter) with 24 VDC. It is mounted on a DIN rail, U and G profile. The device power supply is 230 V ± 15 %, and consumption is about 5 VA.
Linearity is ±0.2 %, the time constant 200–300 ms, and ripple less than 0.2 % of the maximum output signal. Ambient temperature may be from −10 to +65 °C.
Technical data
| Type | UN-PSG |
|---|---|
| Mounting | Mounting on 35 mm DIN rail |
| Housing | 40x90x108 mm |
| Power supply, consumption | 230 V, ±15%, approx. 5 VA |
| Input | 0-20 mA 4-20 mA 0-60 mV 1-5-10 V Thermocouples (L, J, K, S) |
| Output | 0-1 mA 0-20 mA, 4-20 mA 0-1 V, 0-10 V |
| Supply voltage for two-wire transmitter | 16.5 - 18 V/40 mA |
| Internal voltage drop (for current output) | =< 0.5 V |
| Short-circuit current | Ik =< 35 mA |
| Max. permitted external capacitance | Ca =< 320 nF |
| Max. permitted external inductance | La =< 25 mH |
| Input/output isolation voltage | 1500 V |
| Loop (for current output) | 0 - 600 ohm |
| Output current limit | < 27 mA |
| Time constant | 200 - 300 ms |
| Ripple | < 0.2 % of max. output signal |
| Linearity | ±0.2 % |
| Loop influence | ±0.1 % of output signal span / 700 ohm |
| Ambient temperature | -10 to +65 ºC |
| Ambient temperature influence | ±0.2 % of output signal span / 10 K change |
| Power supply influence | ±0.2 % of output signal span / 15 % change |
| Output voltage | 24 VDC/40mA |
| Maximum output current | 40 mA |
| Output signal limit | 24 mA or 15 V |
| Loop load | Approx. 600 ohm |
Dimensions
The drawings are taken from the technical documentation.
Documentation
01Technical documentation1
Help with selection
Describe your application and we will suggest a version and a catalogue number.
For an accurate reply, please state in your enquiry:
- 01The medium and its temperature
- 02Measuring range
- 03Output signal or power supply
- 04Type of mounting and connection