Flow computer, integrator and square-root extractor
INP-06, INP-08, INK-06
Devices for measuring, displaying and totalising the flow of steam, gases and other fluids. They show the instantaneous flow and the cumulative total, and the INK-06 flow computer corrects the flow for pressure and temperature.
- Instantaneous flow and cumulative total, 8-digit resettable totaliser
- Optional 6-digit electromechanical counter
- Flow correction for pressure and temperature (INK-06)
- Up to 8 programmable alarms
- Data logging to a USB stick or SD card
- RS-485 Modbus for process monitoring
Why INP-06, INP-08, INK-06
- 01
Steam mass flow
INK-06 calculates mass flow from volume flow, corrected for pressure and temperature, with a differential pressure transmitter.
- 02
Flow and cumulative total
Two internal 8-digit counters, one resettable, and the option of an external electromechanical counter.
- 03
Process record
Logged data are transferred to a computer via RS-485 or a USB stick and opened as a chart or table, e.g. in Excel.
Description
Integrators, square root extractors and the flow computer measure, display and totalise the instantaneous flow and the cumulative flow over a given time. They can measure steam, gases, fluids, energy and temperature.
INP-06 is an integrator for measuring the flow of steam and gases with a differential pressure transmitter, vortex meter and similar sensors. It shows the flow on an LED display and the cumulative total on an electromechanical counter. An alarm can be enabled that closes the valve when the flow is too high.
INP-08 is an integrator for measuring steam and gases with a differential pressure transmitter, vortex meter and similar sensors. It shows the flow and the cumulative total on an LED display. It has two internal 8-digit counters, one resettable, and the option of fitting an external electromechanical counter.
INK-06 is a steam flow computer with a differential pressure transmitter. It calculates mass flow from volume flow corrected for temperature and pressure, which gives higher measurement accuracy.
The measured value can be scaled, galvanically isolated and passed to the analogue output, as an input to another instrument. The processed signal is compared with the set parameters, and the process state and disturbances are signalled at the logic or relay output and by indicator lights on the front panel. An audible alarm with acknowledgement is supported.
Process records are transferred to a computer via an RS-485 network or a USB stick. They are displayed as a chart or table and processed further in Microsoft Excel or another spreadsheet, and printed on a USB printer if required. The settings are password-protected.
Technical data
Version comparison — swipe the table sideways on a phone.
| Property | INP - 08 | INP - 06 | INK-06 |
|---|---|---|---|
| Front panel | Membrane keypad | Membrane keypad | Membrane keypad |
| Mounting | Panel with cut-out | Panel with cut-out | Panel with cut-out |
| Housing | 96x96 mm 72x72 mm 144X72 mm 72x144 mm 105x90x58 mm DIN rail | 72x72 mm 144x72 mm 72x144 mm | 96x96 mm 144X72 mm 72x144 mm |
| Power supply | 230 VAC 24 VDC 24 VAC 110 VAC | 230 VAC 24 VDC 24 VAC 110 VAC | 230 VAC 24 VDC 24 VAC 110 VAC |
| Class | 0.2 % of full scale (in the range 0-100%) | 0.2 % of full scale (in the range 0-100%) | 0.3 % of full scale (in the range 5-100%) |
| Input | Input 1:RTD: Pt100/200, Ni100/200, Pt100 psychrometer, Cu53, RTD linearisation in 25 points, potentiometer , voltage: 0-50mV, 0-60 mV, thermocouples: L, J, K, S, R, T, N, E, B, current: 0/4 -20 mA, 20-4/0 mA | Input 1:RTD: Pt100/200, Ni100/200, Pt100 psychrometer, Cu53, RTD linearisation in 25 points, potentiometer , voltage: 0-50mV, 0-60 mV, thermocouples: L, J, K, S, R, T, N, E, B, current: 0/4 -20 mA, 20-4/0 mA | Input 1:RTD: Pt100/200, Ni100/200, Pt100 psychrometer, Cu53, RTD linearisation in 25 points, potentiometer , voltage: 0-50mV, 0-60 mV, thermocouples: L, J, K, S, R, T, N, E, B, current: 0/4 -20 mA, 20-4/0 mA |
| Output | 0/4 - 20 mA 0/1 - 5 V 0/2 - 10 V | 0/4 - 20 mA 0/1 - 5 V 0/2 - 10 V | 0/4 - 20 mA 0/1 - 5 V 0/2 - 10 V |
| Input connection | Two-wire Three-wire | ------------------------------------------ | Two-wire Three-wire |
| Integrator | internal 8-digit resettable counter | internal 8-digit resettable counter / 6-digit electromechanical counter | 6-digit electromechanical counter |
| Output load | 500 ohm | 500 ohm | 500 ohm |
| Temperature influence | 0.03 % / K | 0.03 % / K | 0.03 % / K |
| Error due to power supply | 0.01% of full scale at mains ±15% | 0.01% of full scale at mains ±15% | 0.01% of full scale at mains ±15% |
| Display | Measured value shown on a 4- and 5-digit LED display. Unit of measure shown on a 3-digit LED display | 13 mm red LED display, 4 digits | LCD display 4/5 digits |
| Alarm | Up to 8 programmable alarms | Up to 8 programmable alarms | ------------------------------------------- |
Application examples
Documentation
01Technical documentation1
Help with selection
Describe your application and we will suggest a version and a catalogue number.
For an accurate reply, please state in your enquiry:
- 01The medium and its temperature
- 02Measuring range
- 03Output signal or power supply
- 04Type of mounting and connection
Enquiry forINP-06, INP-08, INK-06Cat. no. E17
or contact us directly
Mon – Fri, 7 am – 3 pm