Skip to content
Name, type or catalogue number

    Popular searches

    ↑↓ selectEnter open/ search from any page

    • Reflex VG

    FMCW radar level meter

    Reflex VG

    Radar level meters for liquids and powders in tanks and silos, with a measuring range up to 80 m. The VG series is part of the product range of Hycontrol UK.

    Price from830,00 €+ VAT

    Catalogue number
    Send an enquiry for this product
    • Measuring range from 20 m to 80 m, depending on type
    • FMCW, nominal frequency 26 GHz
    • Display of level, distance or volume on the meter
    • Output 4–20 mA, two-wire power supply 24 VDC (VG502: 100–230 VAC)
    • HART, optionally Profibus PA or Foundation Fieldbus
    • Versions with ATEX EExia and EExd approval
    ApplicationsLevel

    Why Reflex VG

    • 01

      Up to 80 m, liquids and solids

      VG6 measures solids up to 80 m, VG7 liquids and solids up to 40 m, VG502 liquids up to 35 m, and VG50 and VG51 liquids up to 20 m.

    • 02

      HART, Profibus PA, Fieldbus

      All types have 4–20 mA output and HART, and optionally Profibus PA or Foundation Fieldbus. The meter has an HMI display.

    • 03

      Ex and high temperatures

      Versions for explosive zones (ATEX EExia and EExd) and for temperatures up to 250 °C and pressure up to 64 bar, depending on type.

    Description

    VG series radars measure the level of liquids, powders and waste water in tanks and silos.

    The antenna emits a radar signal that travels through the air in the vessel to the surface of the medium, is reflected and returns to the antenna. FMCW radar (Frequency Modulated Continuous Wave) uses a high-frequency signal with a nominal frequency of 26 GHz, which increases linearly during the measurement (frequency sweep).

    The reflected signal returns to the receiver with a time delay. The difference between the transmitted and received frequencies is calculated, and it is directly proportional to the measured distance.

    Advantages of the FMCW principle compared with pulse radar:

    • better separation of reflections
    • more reliable noise suppression
    • smaller beam angle
    • less interference from reflections
    • smaller antenna diameter for the same measuring range

    The display on the meter shows level, distance or volume. The meter is not sensitive to noise, e.g. in silos with stone, or to dust clouds when emptying silos with powders. It is easy to fit on existing and new tanks and silos.

    There are versions for explosive zones (EExd and EExia) and for elevated temperatures and pressures. Communication: HART, Profibus PA and Foundation Fieldbus.

    Application:

    • cement silos
    • flour and wheat silos
    • water and oil tanks
    • waste water

    The Reflex VG series radar is part of the product range of Hycontrol UK.

    Technical data

    Version comparison — swipe the table sideways on a phone.

    PropertyVG50VG51VG502VG6VG7
    MaterialsLiquidsLiquidsLiquidsSolidsLiquids, solids
    Operating modeDirect / TBFDirect / TBFDirect / TBFDirectDirect / TBF
    AntennaHornWavestick ('rod')HornDN80, DN100, DROP ('egg')DN40, DN50, DN80
    Measuring range20 m20 m35 m80 m40 m
    Accuracy0,30%0,30%1 mm10 mmliquids 3mm
    solids 10mm
    Max. temperature250 °C150 °C250 °C100 - 200 °C200 °C
    Max. pressure [bar]64 bar16 bar64 bar16 bar or 40 bar40 bar
    Process connectionFlange 3"G 1 1/2"Flange 8"G1"
    G1 1/2"
    G3"
    G4"
    Flange DIN
    G1 1/2"
    G3"
    G4"
    Flange DIN
    Dielectric constant (Er)>2>4>2>1,5>1,5
    Output4 - 20 mA4 - 20 mA4 - 20 mA4 - 20 mA4 - 20 mA
    Power supply2-wire, 24 Vdc2-wire, 24 Vdc4-wire, 100-230 VAC2-wire, 24 Vdc2-wire, 24 Vdc
    DisplayHMI DisplayHMI DisplayHMI DisplayHMI DisplayHMI Display
    CommunicationHART;
    Profibus PA, Fieldbus (optional)
    HART;
    Profibus PA, Fieldbus (optional)
    HART, PACTWARE, RS485;
    Profibus PA, Fieldbus (optional)
    HART, PACTWARE;
    Profibus PA, Fieldbus (optional)
    HART, PACTWARE;
    Profibus PA, Fieldbus (optional)
    ApprovalsATEX EExia
    ATEX EExd
    ATEX EExia
    ATEX EExd
    ATEX EExdATEX EExia
    ATEX EExd
    ATEX EExia
    ATEX EExd

    Application examples

    Documentation

    Help with selection

    Describe your application and we will suggest a version and a catalogue number.

    For an accurate reply, please state in your enquiry:

    1. 01The medium and its temperature
    2. 02Measuring range
    3. 03Output signal or power supply
    4. 04Type of mounting and connection
    Enquiry forReflex VGCat. no. VG
    Send an enquiry

    or contact us directly

    Mon – Fri, 7 am – 3 pm