Level switch with four electrodes
SN-4
Level switch for four levels of conductive liquids, or for level control with hysteresis and additional signalling of two levels (e.g. MIN and MAX). It has four relay outputs 5 A / 250 V.
Price from1.130,00 €+ VAT
Needed to operate
The signal from the tank comes from PI conductive probes, mounted in the tank, boiler or pipeline.
- Signalling of up to 4 levels
- Control with hysteresis and MIN and MAX alarms
- 4 relay outputs 5 A, 250 V
- Sensitivity 5–50 kΩ, four trimmers
- Power supply 230 VAC, 24 VDC or 24 VAC
- Housing 105 × 90 mm for DIN rail or 96 × 48 mm for panel
Description
SN-4 is intended for signalling of four levels or level control with hysteresis, with optional additional signalling of two levels (e.g. MIN and MAX), for driving signalling devices, and as an additional device for burner shut-down at low water level in a steam boiler.
It is supplied in two housing types: for DIN-rail mounting and for mounting in a panel cut-out. The front panel carries indicator lights for the four levels, an ON operation indicator and four trimmers for sensitivity adjustment. The terminals are at the top and bottom, and at the rear on the panel housing.
It is designed for liquids of higher conductivity, such as water in hot-water and steam boilers, storage reservoirs, thermal baths and municipal water supply.
Technical data
| Type | SN-4 |
|---|---|
| Mounting | DIN-rail mounting Panel with cut-out |
| Dimensions | 105x90 mm [DIN rail] 96x48 mm [panel] |
| Output | 4 x relay 5A, 250 V |
| Power supply | 230 VAC 24 VDC 24 VAC |
| Power consumption | Approx. 4 VA |
| Sensitivity | 5 - 50 kohm |
| Number of electrodes | Earth + 1-4 electrodes |
| Operating temperature | - 10 to + 60 *C |
Dimensions
The drawings are taken from the technical documentation.
Application examples
Documentation
01Technical documentation1
Help with selection
Describe your application and we will suggest a version and a catalogue number.
For an accurate reply, please state in your enquiry:
- 01The medium and its temperature
- 02Measuring range
- 03Output signal or power supply