Paperless recorder
VR06
Paperless recorder with one to six configurable universal inputs and a 6.4" TFT display with 640 × 480 resolution. It stores data in the 8 MB internal memory and on a card, and communicates with a PC via Ethernet or RS-232/485.
- 6.4" colour TFT LCD, 640 × 480 pixels
- 1–6 universal analogue inputs
- 6 relay outputs 5 A / 240 VAC
- Ethernet (Modbus TCP), optional RS-232/485 (Modbus RTU)
- Five display modes for current data
- Housing 144 × 144 mm for panel mounting
Why VR06
- 01
Universal inputs
Thermocouples J, K, T, E, B, R, S, N and L, Pt100 and mV, mA and 0–1, 0–5, 1–5 and 0–10 V signals, configurable on each of up to six channels.
- 02
Five display modes
Up to six real-time graphs, horizontal or vertical, bargraphs and numeric values alongside the graphs, alarm screen and memory status.
- 03
Ethernet and Modbus
Ethernet with the Modbus TCP protocol is built in as standard. The optional CM181 module adds RS-232 or RS-485/422 with Modbus RTU, up to 247 devices.
Description
VR06 is a paperless recorder with a 6.4" display, resolution 640 × 480 (true VGA), an infrared detector, six channels and plug & play I/O cards. It is used for monitoring, recording and evaluating processes in plants.
It is applied in chemical plants, food and beverage production, petrochemicals, the metal industry, the automotive industry, environmental monitoring and laboratories.
An Ethernet port is built in as standard; RS-232/485 is an option. Data is transferred to a PC by card or communication. The Observer I software for viewing and saving data comes with the recorder, and real-time viewing is provided by the additional Observer II software.
Display modes:
- five display modes for current data
- six real-time graphs, horizontal or vertical
- bargraph and numeric values combined with graphs
- alarm screen and memory status
- simple change of screen layout
Internal memory is 8 MB, card memory 512 MB or 1 GB. Power supply is 90–250 VAC or 11–18, 18–36 or 36–72 VDC, 30 W maximum. Operating temperature is 5 to 50 °C at a humidity of 20 to 80 % RH, non-condensing. Protection is IP30 for the front panel and IP20 for the housing.
Technical data
| Type | VR06 |
|---|---|
| Mounting | Panel with cut-out |
| Housing | 144x144 mm |
| Power supply | 90-250VAC, 60VA, 30W maximum 11-18, 18-36 or 36-72 VDC 60VA, 30W maximum |
| Display | 6.4'' TFT LCD, 640x480 pixel resolution, 256 colours |
| Analogue inputs | type J -120ºC-1000ºC +/- 1ºC type K -200ºC-1370ºC +/-1ºC type T -250ºC-400ºC +/-1ºC type E -100ºC-900ºC +/-1ºC type B 0ºC-1820ºC +/-2ºC type R 0ºC-1767.8ºC +/-2ºC type S 0ºC-1767.8ºC +/-2ºC type N -250ºC-1300ºC +/-1ºC type L -200ºC-900ºC +/-1ºC PT100 -210ºC-700ºC PT100 -200ºC-600ºC mV -8mV-70mV mA -3mA-27mA 0-1V -0.12V-1.15V 0-5V -1.3V-11.5V 1-5V -1.3V-11.5V 0-10V -1.3V-11.5V |
| Analogue outputs | Output signal: 4-20mA, 0-20mA 0-5V, 1-5V, 0-10V |
| Digital inputs | L06"0"- -5V to 0.8V L06"1"- 2V to 5V |
| Digital outputs | 6 channels N.O contact (form A) relay 5A/240 VAC |
| Memory | Internal- 8MB, cards- 512MB, 1GB |
| Communication | 1. Standard Ethernet communication Protocol: Mod Bus TCP / IP BaseT, wrong-polarity correction for 10 BaseT 2. COMM module (CM181) RS-232 (1 device), RS-485 or RS-422 (up to 247 devices) Protocol: Modbus protocol RTU mode Address: 1-247 |
| Operating conditions | Operating temperature: 5ºC to 50ºC Humidity: 20 to 80% RH (non-condensing) |
| Protection | IP30- Front panel IP20- Housing |
Application examples
Help with selection
Describe your application and we will suggest a version and a catalogue number.
For an accurate reply, please state in your enquiry:
- 01The medium and its temperature
- 02Measuring range
- 03Output signal or power supply
- 04Type of mounting and connection