Digital indicator with alarm outputs, 16 channels
EDPS-16
Device for monitoring up to 16 measuring points with galvanically isolated, software-configurable universal inputs. You set two alarm limits for each channel; when a limit is exceeded, the visual alarm and the output relays switch on.
- 16 universal, galvanically isolated inputs
- MIN and MAX alarms, separately for each channel
- Two output relays, audible and visual alarm
- Channel switching from 1 to 255 s
- Optional RS-485 Modbus
- Housing 144 × 72 or 72 × 144 mm
Why EDPS-16
- 01
16 universal inputs
Galvanically isolated inputs for 0/4–20 mA, 0–10 V, mV, thermocouples K, L, N, E, S, R, T, B, J, and Pt100–Pt1000, Ni100–Ni1000 and Cu53. The number of channels switched is adjustable.
- 02
Alarm for each channel
You set the MIN and MAX limits separately for each channel. When a limit is exceeded, the visual alarm and the output relays switch on until the value returns within the limits.
- 03
Modbus to the supervisory system
An optional RS-485 interface with the Modbus protocol connects the device to a supervisory computer. The input signal is digitally filtered, and you adjust the filtering level to suit the interference in the plant.
Description
EDPS-16 is intended for monitoring up to 16 input measuring points. The analogue input is universal and software-configurable, and the inputs are galvanically isolated from each other. The switching time of each input is adjustable from 1 to 255 seconds.
Parameters are entered using the keypad on the front panel. Two alarm limits are set for each channel. When the measured value exceeds the set limit, a visual alarm appears on the front panel and the output relays switch on. The alarm lasts until the measured value returns within the set limits.
The input quantity is sampled, measured and then digitally filtered to remove electrical interference from power equipment in the plant. During parameter setting you can decrease or increase the filtering, depending on the interference level.
The number of channels switched is also software-configurable. The front panel has a four-digit display of the measured value, a two-digit channel display and 16 LEDs for the alarm per channel. The device is made in standard DIN housings 144 × 72 and 72 × 144 mm, with a power supply of 230 VAC, 110 VAC, 24 VAC or 24 VDC.
Technical data
| Type | EDPS-16 |
|---|---|
| Front panel | Membrane keypad |
| Mounting | Panel with cut-out |
| Housing | 144x72 mm 72x144 mm |
| Power supply | 230 VAC 24 VDC 24 VAC 110 VAC |
| Display | 13 mm red LED display, 4 digits 13mm red LED display, 2 digits 16 LEDs |
| Input | 16x Universal - software-configurable Current: 0/4 -20 mA / 4-20mA / 20-0 mA / 20-4mA Voltage: 0-10 V / 2-10 V / 0-50mV / 0-60 mV Thermocouples: K, L, N, E, S, R, T, B, J Resistance: Pt100/200/500/1000, Ni100/200/500/1000, Cu53, potentiometers Other: (PWM signal, frequency) on special request |
| Output | Relay |
| Class | 0.3% + 2 digits |
| Function | Display of the measured quantity. Setting of limit values. Alarm (volt-free contact). Switching on of the audible and visual alarm. |
| Alarm type | Min and max |
| Alarm level | Adjustable for each channel (two alarm levels) |
| Connection between inputs | Galvanically isolated |
| Option | RS 485 communication Modbus protocol |
Dimensions
The drawings are taken from the technical documentation.
Application examples
Documentation
01Technical documentation1
From the same category
Indicators and alarm unitsHelp with selection
Describe your application and we will suggest a version and a catalogue number.
For an accurate reply, please state in your enquiry:
- 01The medium and its temperature
- 02Measuring range
- 03Output signal or power supply
- 04Type of mounting and connection