    Device for monitoring up to 16 measuring points with galvanically isolated, software-configurable universal inputs. You set two alarm limits for each channel; when a limit is exceeded, the visual alarm and the output relays switch on.

    Price from340,00 €+ VAT

    Catalogue number Dimensions
    Send an enquiry for this product
    • 16 universal, galvanically isolated inputs
    • MIN and MAX alarms, separately for each channel
    • Two output relays, audible and visual alarm
    • Channel switching from 1 to 255 s
    • Optional RS-485 Modbus
    • Housing 144 × 72 or 72 × 144 mm

    Why EDPS-16

    • 01

      16 universal inputs

      Galvanically isolated inputs for 0/4–20 mA, 0–10 V, mV, thermocouples K, L, N, E, S, R, T, B, J, and Pt100–Pt1000, Ni100–Ni1000 and Cu53. The number of channels switched is adjustable.

    • 02

      Alarm for each channel

      You set the MIN and MAX limits separately for each channel. When a limit is exceeded, the visual alarm and the output relays switch on until the value returns within the limits.

    • 03

      Modbus to the supervisory system

      An optional RS-485 interface with the Modbus protocol connects the device to a supervisory computer. The input signal is digitally filtered, and you adjust the filtering level to suit the interference in the plant.

    Description

    EDPS-16 is intended for monitoring up to 16 input measuring points. The analogue input is universal and software-configurable, and the inputs are galvanically isolated from each other. The switching time of each input is adjustable from 1 to 255 seconds.

    Parameters are entered using the keypad on the front panel. Two alarm limits are set for each channel. When the measured value exceeds the set limit, a visual alarm appears on the front panel and the output relays switch on. The alarm lasts until the measured value returns within the set limits.

    The input quantity is sampled, measured and then digitally filtered to remove electrical interference from power equipment in the plant. During parameter setting you can decrease or increase the filtering, depending on the interference level.

    The number of channels switched is also software-configurable. The front panel has a four-digit display of the measured value, a two-digit channel display and 16 LEDs for the alarm per channel. The device is made in standard DIN housings 144 × 72 and 72 × 144 mm, with a power supply of 230 VAC, 110 VAC, 24 VAC or 24 VDC.

    Technical data

    TypeEDPS-16
    Front panelMembrane keypad
    MountingPanel with cut-out
    Housing144x72 mm
    72x144 mm
    Power supply230 VAC
    24 VDC
    24 VAC
    110 VAC
    Display13 mm red LED display, 4 digits
    13mm red LED display, 2 digits
    16 LEDs
    Input16x Universal - software-configurable
    Current: 0/4 -20 mA / 4-20mA / 20-0 mA / 20-4mA
    Voltage: 0-10 V / 2-10 V / 0-50mV / 0-60 mV
    Thermocouples: K, L, N, E, S, R, T, B, J
    Resistance: Pt100/200/500/1000, Ni100/200/500/1000, Cu53, potentiometers
    Other: (PWM signal, frequency) on special request
    OutputRelay
    Class0.3% + 2 digits
    FunctionDisplay of the measured quantity.
    Setting of limit values.
    Alarm (volt-free contact).
    Switching on of the audible and visual alarm.
    Alarm typeMin and max
    Alarm levelAdjustable for each channel (two alarm levels)
    Connection between inputsGalvanically isolated
    OptionRS 485 communication
    Modbus protocol

    Dimensions

    The drawings are taken from the technical documentation.

    Application examples

    Documentation

    01Technical documentation1

    Help with selection

    Describe your application and we will suggest a version and a catalogue number.

    For an accurate reply, please state in your enquiry:

    1. 01The medium and its temperature
    2. 02Measuring range
    3. 03Output signal or power supply
    4. 04Type of mounting and connection
    Enquiry forEDPS-16Cat. no. 0163.