Frequency to standard signal converter
MPF-U4S
Converter of frequency, e.g. rotational speed, into a standard current or voltage signal. It measures from 0.001 Hz to 5000 Hz and adapts the measuring method to the frequency by itself.
- Measuring range 0–5000 Hz
- Low frequencies with 0.001 Hz sensitivity, high frequencies with 1 Hz
- Output 0–20 mA, 4–20 mA, 0–10 V, 2–10 V or PWM
- Open-collector alarm output
- Housing 52 × 90 mm for DIN-rail mounting
- Consumption approx. 4 VA
Description
MPF-U4S is used in systems and plants where frequency, e.g. rotational speed, has to be measured and converted into a standard measuring signal.
Depending on the frequency, the device measures by one of two methods:
- method 1: counting pulses within 1 s, with 1 Hz resolution; the measuring range is 0–5 kHz
- method 2, for lower frequencies: measuring the period T between two pulses, with the frequency calculated as f = 1/T; the resolution is 1 ms and the measuring range 0.001–25 Hz
Above 25 Hz the device automatically switches from method 2 to method 1, and when the frequency drops below 20 Hz it returns to method 2.
The output is current (0–20 mA, 4–20 mA), voltage (0–10 V, 2–10 V) or PWM; other outputs are made on special request.
Technical data
| Type | MPF-U4S |
|---|---|
| Mounting | DIN-rail mounting |
| Housing | 52x90 mm |
| Input | Frequency |
| Output | Current - 0-20 mA, 4-20 mA Voltage - 0-10 V, 2-10 V Resistive - PWM Other - on special request |
| Power consumption | approx. 4 VA |
| Sensitivity | 0.001Hz - 5000Hz |