    Guided radar (TDR) for level measurement

    Reflex VF

    Guided radar for level measurement of liquids, powders and granules up to 35 m. The VF series is part of the product range of Hycontrol UK.

    Price820,00 €+ VAT

    Send an enquiry for this product
    • Measuring range up to 24 m (VF03) or 35 m (VF7)
    • Accuracy 3–5 mm for liquids, 20 mm for powders
    • Up to 300 °C and 100 bar (VF7)
    • Two-wire power supply 24 VDC, output 4–20 mA, HART
    • Measurement through foam and in dusty atmospheres
    • ATEX EExia and EExd approvals

    Description

    The Reflex VF series of TDR radars measures the level of liquids, powders and granules over a range up to 35 m. The measurement is not affected by changes in pressure, temperature, viscosity, vacuum, foam, dust and dielectric constant, or by deposits on the probe.

    The meter operates in direct (Direct) or TBF mode, with one of seven probe types.

    Low-voltage microwave pulses are sent along a conductor. When the wave reaches the surface of the medium, it is reflected and returns to the meter. The intensity of the reflection depends on the dielectric constant of the medium: the higher it is, the stronger the reflection, e.g. up to 80 % for water. The device measures the time from sending the wave to its return, which is proportional to the distance.

    Application:

    • cement silos
    • flour and wheat silos
    • water and oil tanks
    • waste water

    The Reflex VF series guided radar is part of the product range of Hycontrol UK.

    Technical data

    Version comparison — swipe the table sideways on a phone.

    PropertyVF03VF7
    MaterialsLiquids, solids, powdersLiquids, solids, powders
    Operating modeDirectDirect / TBF
    Measuring range3 m - 24 m4 m - 35 m
    Accuracy5 mm - liquids
    20 mm - powders
    3 mm - liquids
    20 mm - powders
    Max. temperature200°C300 °C
    Max. pressure40 bar100 bar
    Process connectionFlanges (standard) DIN, G1", G 1 1/2" ,G 2",G 3", ...Flanges (standard) DIN, G 3/4", G1", G 1 1/2" ,
    G 2",G 3", ...
    Dielectric constant> 1,61,4 / 1,1
    Output4-20 mA two-wire4-20 mA two-wire
    Power supplyTwo-wire, 24 Vdc (17-30 Vdc)Two-wire, 24 Vdc (17-30 Vdc)
    DisplayWithout displayWith display
    CommunicationHARTHART, Profibus PA, Fieldbus
    ApprovalsATEX EExiaATEX EExia
    ATEX EExd

    Application examples

    Documentation

    01Brochures and catalogues1
    02Wiring diagrams and examples1

    Help with selection

    Describe your application and we will suggest a version and a catalogue number.

    For an accurate reply, please state in your enquiry:

    1. 01The medium and its temperature
    2. 02Measuring range
    3. 03Output signal or power supply
    4. 04Type of mounting and connection
    Enquiry forReflex VFCat. no. VF03
    Send an enquiry

    or contact us directly

    Mon – Fri, 7 am – 3 pm