Disc-type flow transmitter
MPQ
Flow transmitter for liquids with a moving disc, for pipelines up to DN 200 and flow up to 4000 l/min. The output is a 4–20 mA current signal proportional to the flow.
- Measuring ranges from 2–6 l/min to 800–4000 l/min
- Connections DN 15 to DN 200: screw-in, threaded or flanged
- Output 4–20 mA, three-wire connection, power supply 18–30 V
- Class 2 % in the 20–100 % range
- Operating pressure up to 16 bar, with flange up to 40 bar
- High-temperature version up to 300 °C, material W.Nr. 1.4571
Description
MPQ is a disc-type flow transmitter for measuring the flow of liquids in pipelines with a nominal bore of up to 200 mm, i.e. up to a flow of 4000 l/min.
The force of the medium flow moves the disc, which changes the electrical properties of the measuring magnet. The electronics convert these changes into a standard current signal proportional to the flow in the pipe.
The transmitter is made with three standard connections, screw-in, threaded and flanged, and with another connection on customer request. The standard version operates with media up to 60 °C, and the version for elevated temperatures up to 300 °C.
The pressure drop is 0.4 bar at most, and negligible with the screw-in version. Hysteresis is 0.5 %, and the ambient temperature influence 0.05 %/K.
Technical data
Version comparison — swipe the table sideways on a phone.
| Property | MPQ | MPQ | MPQ |
|---|---|---|---|
| Device name | Flow transmitter with screw-in connection | Flow transmitter with threaded connection | Flow transmitter with flange |
| Power supply | 18-30 V | 18-30 V three-wire | 18-30 V three-wire |
| Input | Flow | Flow | Flow |
| Output | 4-20 mA | 4-20 mA | 4-20 mA |
| Medium temperature | Up to 60 ºC | 0 to 60 ºC | 0 to 60 ºC 0 to 300 ºC [high-temperature version] |
| Class | 2% / 20-100% | 2% / 20-100% | 2% / 20-100% |
| Operating pressure | Up to 16 bar | Up to 16 bar | Up to 40 bar |
| Pressure drop | Negligible | Max 0.4 bar | Max 0.4 bar |
| Influence of ambient temperature change | 0.05% / ºK | 0.05% / ºK | 0.05% / ºK |
| Influence of pipe diameter change | The error increases with the square of the diameter change | — | — |
| Hysteresis | — | 0.5 % | 0.5 % |
Documentation
01Technical documentation1
Help with selection
Describe your application and we will suggest a version and a catalogue number.
For an accurate reply, please state in your enquiry:
- 01The medium and its temperature
- 02Measuring range
- 03Output signal or power supply
- 04Type of mounting and connection